| Customization: | Available |
|---|---|
| Sprinkler Installation: | UL Listed Fire Sprinkler |
| Sprinkler Head Type: | UL Listed Fire Sprinkler |
| Shipping Cost: | Contact the supplier about freight and estimated delivery time. |
|---|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
The Pendent Quick Response Glass Bulb Fire Sprinkler is a high-speed automatic fire suppression device designed for use in commercial, institutional, and residential fire sprinkler systems where rapid response is essential. This pendent model hangs downward from the ceiling piping and distributes water in a hemispherical pattern to protect the area below.
The sprinkler incorporates a sensitive 3mm JOB brand glass bulb filled with glycerin solution. The smaller diameter of the bulb allows for quicker heat absorption and faster activation compared to standard response models, making it ideal for environments such as hospitals, hotels, schools, and office buildings where early fire detection can save lives. When the ambient temperature reaches 155 degree F (68 degree C), the red liquid expands, shattering the bulb and releasing the sealing assembly. Water then flows through the K5.6 orifice and strikes the deflector, producing a uniform spray pattern for effective fire control.
Constructed from high-quality brass forging copper alloy, this sprinkler offers excellent durability and corrosion resistance. The compact design facilitates easy installation in standard ceiling configurations. With UL Listed, FM Approved, and CE Certified credentials, this sprinkler meets the most stringent safety and quality standards required by insurance companies and regulatory authorities worldwide. The 1/2 inch NPT or R 1/2 thread connection ensures compatibility with common fire sprinkler piping systems.
Ideal for protecting hospitals, hotels, schools, office buildings, restaurants, and other life-safety-focused occupancies, this pendent quick response sprinkler delivers reliable, automatic fire protection with the speed needed to minimize damage and protect occupants.
| Attribute | Specification |
|---|---|
| Model Type | Pendent Quick Response |
| Certification | UL Listed, FM Approved, CE Certified |
| K-Factor | 5.6 (80 metric) |
| Thread Size | NPT 1/2 or R 1/2 (BSPT) |
| Max Service Pressure | 175 psi (12 bar) |
| Glass Bulb Diameter | 3 mm |
| Glass Bulb Brand | JOB |
| Glass Bulb Liquid | Glycerin Solution |
| Activation Temperature | 155 degree F (68 degree C) |
| Glass Bulb Color | Red |
| Body Material | Brass Forging Copper Alloy |
| Deflector Material | Brass |
| Seal Material | NBR |
| Minimum Operating Pressure | 7 psi (0.5 bar) |
| Factory Test Pressure | 500 psi (35 bar) |
| Response Type | Quick Response |
| Installation Type | Pendent |
| Application | Commercial / Institutional / Residential |
Q1: What certifications does this pendent quick response sprinkler hold?
A1: It is UL Listed, FM Approved, and CE Certified.
Q2: What is the K-Factor?
A2: The K-Factor is 5.6 (80 metric).
Q3: What thread sizes are available?
A3: NPT 1/2 or R 1/2 (BSPT) thread connections.
Q4: What is the maximum service pressure?
A4: 175 psi (12 bar).
Q5: What glass bulb brand and diameter are used?
A5: JOB brand with 3 mm diameter.
Q6: What is the activation temperature?
A6: 155 degree F (68 degree C), indicated by the red glass bulb.
Q7: What is the difference between quick response and standard response?
A7: Quick response sprinklers have a smaller glass bulb (3mm vs 5mm) and activate faster, making them suitable for areas where early fire suppression is critical for life safety.
Q8: Where is this pendent model installed?
A8: Pendent sprinklers hang downward from ceiling pipes and are used in areas with finished ceilings.
Q9: What material is the sprinkler body made of?
A9: Brass forging copper alloy with corrosion-resistant finish.
Q10: What is the minimum operating pressure?
A10: 7 psi (0.5 bar).